DigiStano

MV & HV Cables Testing Solutions

PD60-2 & PDTD60-2

Advanced PD and Tan Delta diagnostics for medium and high-voltage cable systems

Portable and built-in solutions for diagnostics of medium voltage cables, rotating machines and transformers, enabling early detection of vulnerabilities and preventative maintenance before failure occurs in service.

PD60-2 & PDTD60-2

Product Highlights

Comprehensive PD and Tan Delta diagnostics for cable systems

PD60-2 and PDTD60-2 support accurate defect localization, simultaneous diagnostics, and condition assessment for a wide range of cable assets and insulation systems.

Portable and built-in solutions for diagnostics of medium voltage cables, rotating machines and transformers

Supports early detection of vulnerabilities before cable failure in service

PDTD60-2 includes integrated Tan Delta diagnostics

Provides simultaneous comprehensive PD and TD diagnostics

Suitable for testing XLPE, PE, EPR and PILC cables up to 100 km

Precise PD fault localization with 1% accuracy and 0.1 pC per 0.1 m resolution

Description

Comprehensive cable diagnostics and PD localization

The PD60-2 and PDTD60-2 offer both portable and built-in solutions for diagnostics of medium voltage cables, rotating machines and transformers.

Diagnostics of medium and high voltage cables provides the opportunity for early detection of vulnerabilities and preventative maintenance work to be carried out before the cable fails in service.

Performance

PDTD60-2 includes integrated Tan Delta diagnostics capabilities and thus features simultaneous comprehensive PD and TD diagnostics, saving time and avoiding preconditioning of the cable, which would lead to false results.

Comprehensive diagnostics

PDTD60-2 allows measurement of cables with different lengths at constant frequency, being a prerequisite for the comparison of PD and TD results from previous measurements.

Application

Suitable for testing XLPE, PE, EPR and PILC cables up to 100 km.

PD localization

Precise localization of PD faults in cables with the accuracy 1% and resolution 0.1 pC per 0.1 m.

Complete system

In combination with the HVA60 device (not in scope of supply), PDTD60-2 creates a full-featured and full-value system for 60 kV output voltage scope.

Compliance

PD60-2 and PDTD60-2 devices are in compliance with guides like IEEE 400.2 and 400.3 and standards HD 620, CEI EN 50393, IEC 60270, IEC 60502-2 and their local derivations.

Technical Specifications

Operating voltage (sine wave)

max. 62 kVpeak, 44 kVrms

Capacitance – PD-2 CC

~ 1 nF

Capacitance – PD-2 Filter

~ 1 nF

Velocity range (v/2)

10 – 150 m/μs

PD background level

< 10 pC

Sample rate

250 MS/s

Tan Delta (resolution / accuracy)

1 x 10^-5 / ± 1 x 10^-4