MV & HV Cables Testing Solutions
PD120-2 & PDTD120-2
Advanced PD and Tan Delta diagnostics for cable systems
Portable and built-in solutions for diagnostics of medium voltage cables, rotating machines and transformers, enabling early detection of vulnerabilities and preventive maintenance before failure occurs in service.

Product Highlights
Comprehensive PD and Tan Delta diagnostics for long cable systems
PD120-2 and PDTD120-2 support accurate defect localization, simultaneous diagnostics, and condition assessment for a wide range of cable assets and insulation systems.
Portable and built-in solutions for diagnostics of medium voltage cables, rotating machines, and transformers
Supports early detection of vulnerabilities before cable failure in service
PDTD120-2 includes integrated Tan Delta diagnostics
Provides simultaneous comprehensive PD and TD diagnostics
Suitable for testing XLPE, PE, EPR and PILC cables up to 100 km
Precise PD fault localization with 1% accuracy and 0.1 pC per 0.1 m resolution
Description
Comprehensive cable diagnostics and PD localization
The PD120-2 and PDTD120-2 offer both portable and built-in solutions for diagnostics of medium voltage cables, rotating machines and transformers.
Diagnostics of medium and high voltage cables provides the opportunity for early detection of vulnerabilities and preventative maintenance work to be carried out before the cable fails in service.
Performance
PDTD120-2 includes integrated Tan Delta diagnostics capabilities and thus features simultaneous comprehensive PD and TD diagnostics, saving time and avoiding preconditioning of the cable, which would lead to false results.
Comprehensive diagnostics
PDTD120-2 allows measurement of cables with different lengths at constant frequency, being a prerequisite for the comparison of PD and TD results from previous measurements.
Application
Suitable for testing XLPE, PE, EPR and PILC cables up to 100 km.
PD localization
Precise localization of PD faults in cables with the accuracy 1% and resolution 0.1 pC per 0.1 m.
Complete system
In combination with the HVA120 device (not in scope of supply), PDTD120-2 creates a full-featured and full-value system for 120 kV output voltage scope.
Compliance
PD120-2 and PDTD120-2 devices are in compliance with guides like IEEE 400.2 and 400.3 and standards HD 620, CENELEC 50393, IEC 60270, IEC 60502-2 and their local derivations.
Technical Specifications
Operating voltage (sine wave)
max. 120 kVpeak, 85 kVrms
Capacitance – PD-2 CC
~ 1 nF
Capacitance – PD-2 Filter
~ 1 nF
Velocity range (v/2)
10 – 150 m/μs
PD background level
< 10 pC
Sample rate
200 MS/s
Tan Delta (resolution / accuracy)
1 x 10^-5 / ± 1 x 10^-4